This portable rugged line of AC high voltage test equipment is ideally suited for use in the field or in the laboratory. The 6CP line offers a complete test system in a mobile package. All units in the 6CP line use a combination control and regulator enclosure and a separate high voltage section. The system is equipped with advanced digital metering, and control and protection devices which are easy to use and provide the operator with all necessary information to safely operate the system. The Metering Guard Mode allows accurate measurements of the high voltage test specimen leakage current by bypassing stray capacitive currents.
| Model | 6CP30/15-3 | 6CP50/10-3 | 6CP100/50-7.5 | 6CP120/60-7.5 | 6CP100/50-10 | 6CP120/60-10 | 6CP200/100-10 | |
| Input |
Voltage/Current | 110-120 V, 16 A 220-240 V, 8 A |
110-120 V, 16 A 220-240 V, 8 A |
110-120 V, 30 A 220-240 V, 15 A |
110-120 V, 30 A 220-240 V, 15 A |
220-240 V, 30 A | 220-240 V, 30 A | 220-240 V, 25 A |
| Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | |
| Output |
Voltage/Current | ≈ 0-15 kV, 200 mA ≈ 0-30 kV, 100 mA |
≈ 0-10 kV, 300 mA ≈ 0-50 kV, 60 mA |
≈ 0-50 kV, 150 mA ≈ 0-100 kV, 75 mA |
≈ 0-60 kV, 125 mA ≈ 0-120 kV, 62.5 mA |
≈ 0-50 kV, 200 mA ≈ 0-100 kV, 100 mA |
≈ 0-60 kV, 166 mA ≈ 0-120 kV, 83 mA |
≈ 0-100 kV, 100 mA ≈ 0-200 kV, 50 mA |
| Duty Cycles |
5 min ON/15 min OFF | 3 kVA | 3 kVA | 7.5 kVA | 7.5 kVA | 10 kVA | 10 kVA | 10 kVA |
| 15 min ON/1 hr OFF | 2 kVA | 2 kVA | 5 kVA | 5 kVA | 7.5 kVA | 7.5 kVA | 7.5 kVA | |
| 1 hr ON/1 hr OFF | 1.5 kVA | 1.5 kVA | 3 kVA | 3 kVA | 5 kVA | 5 kVA | 5 kVA | |
| Features |
Compensation | 50% Inductive Reactive | 50% Inductive Reactive | 66% Inductive + Selectable Capacitive Preload |
66% Inductive + Selectable Capacitive Preload |
50% Inductive Reactive | 50% Inductive Reactive | 50% Inductive Reactive |
| Metering Accuracy | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | 0.8% Reading +0.2% Full Scale | |
| Voltmeter Range(s) | 0-15/30 kV | 0-10/50 kV | 0-50/100 kV | 0-60/120 kV | 0-50/100 kV | 0-60/120 kV | 0-100/200 kV | |
| Currentmeter Range(s) | 0-200 µA/2 mA/ 20 mA/200 mA |
0-200 µA/2 mA/ 20 mA/300 mA |
0-200 µA/ 2 mA/ 20 mA/ 200 mA | 0-200 µA/ 2 mA/ 20 mA/ 200 mA | 0-200 µA/ 2 mA/ 20 mA/ 200 mA | 0-200 µA/ 2 mA/ 20 mA/ 200 mA | 0-200 µA/ 2 mA/ 20 mA/ 200 mA | |
| Output | HV Electrode | HV Electrode | HV Electrode | HV Electrode | HV Electrode | HV Electrode | HV Electrode | |
| PD |
PD level | <10 pC | <10 pC | <10 pC | <10 pC | <10 pC | <10 pC | <10 pC |
| Optional up to 100kV | <3 pC | <3 pC | <3 pC | <3 pC | <3 pC | <3 pC | <3 pC | |
| Cables Included |
Power Cable | 10’(3048 mm) | 10’(3048 mm) | 30’(9144 mm) | 30’(9144 mm) | 30’(9144 mm) | 30’(9144 mm) | 30’(9144 mm) |
| Power Interconnect | 10’(3048 mm) | 10’(3048 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | |
| Meter Interconnect | 10’(3048 mm) | 10’(3048 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | |
| Ground | 10’(3048 mm) | 10’(3048 mm) | (2) 20’(6096 mm) each | (2) 20’(6096 mm) each | (2) 20’(6096 mm) each | (2) 20’(6096 mm) each | (3) 30’(9144 mm) ea | |
| Return | 10’(3048 mm) | 10’(3048 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 20’(6096 mm) | 10’(3048 mm) | |
| Divider Metering | n/a | n/a | n/a | n/a | n/a | n/a | 30’(9144 mm) | |
| Paralleling | n/a | n/a | n/a | n/a | n/a | n/a | 10’(3048 mm) |
Safety and Design Features
- 2 or 3 piece designs
- Circuit breaker protection
- External interlock provision
- High voltage On/Off pushbuttons with indicator
- Zero Start interlock
- Manual control of output voltage
- Adjustable overload circuit
- Slow and fast-acting transient protection on all meters and relays
- Digital timer with audible alarm
- Digital multi range metering
- Emergency Off pushbutton with key lockout (excluding model 6CP30 and 6CP50)
- Guard mode for accurate current measurements
- Output overload indicator with reset switch
- All interconnect control and power cables are included
- Cable storage provision
- Operation/maintenance manual