EGIL200 is the first incarnation in a new range of circuit breaker analysers from Megger. It has been designed in close cooperation with global industry reference groups drawing experience from the market leading and hugely successful Megger TM series of circuit breaker analysers.
The emphasis in the development of the EGIL200 has been on ease of use, ensuring that the time spent on setting up measurements is kept to a minimum. As such, with the EGIL200, you can get your test results done in no time.
- Connection to the test object has also been streamlined and with only one hook-up, all following operations or measurements can be made:
- Timing of main and PIR contacts
- Coil current analysis of close, open 1 and 2 coils
- Station voltage measurements
- Motion measurements
- Motor current measurement
- Minimum pickup voltage test for close, open 1 and open 2
SPECIFICATIONS EGIL200
Specifications are valid after 30 minutes warm up time.System time base drift 0.001 % per year.
Specifications are subject to change without notice.
| Environment | |
|---|---|
| Application field | For use in medium and high voltage substations and industrial environments |
| Temperature | |
| Operating | -20 °C to +55 °C (-4 °F to +131 °F) |
| Storage & transport | -30 °C to +70 °C (-40 °F to +158 °F) |
| Humidity | 5 % – 95 % RH, non-condensing |
| Altitude | |
| Operating |
Up to 2000 m (6562 ft) max. 240 V AC / 250 V DC on mains, max. 250 V AC / 300 V DC on CONTROL and TIMING AUX inputs. Between 2000 m (6562 ft) and 5000 m (16404 ft) max. 150 V AC / DC on mains, CONTROL and TIMING AUX inputs |
| CE-marking | |
| LVD | 2014/35/EU |
| EMC | 2014/30/EU |
| RoHS | 2011/65/EU |
| General | |
| Mains input (nominal) | 100 – 240 V AC, 50 / 60 Hz, 120 – 250 V DC |
| Power consumption | 200 VA (max.) |
| Dimensions | 474 x 415 x 214 mm (18.7” 16.3” 8.4”) |
| Weight | 12 kg (26.5 lbs) |
| IP-rating (IEC 60529): | |
| Closed case | IP67 |
| Open case | IP20 |
| Data memory capacity | 1.4 GB, corresponding to up to 6000 basic recordings or up to 1500 advanced recordings |
| Display | |
| 7” (17.8 cm) LCD, Capacitive touch screen | |
| Available languages | English, French, German, Spanish, Swedish, Polish and Chinese |
| Communication interfaces | |
| 3 USB A, 1 USB B for connection to external PC | |
| RJ45 for connection to external PC | |
| Keyboard | On-screen and optional USB keyboard |
| External outputs | |
| Trig output for SDRM20X | |
| Output voltage | 12 V DC ±10 % |
| Short circuit protection | PTC 250 mA |
| Switching current | < 250 mA, resistive load |
| Control section | |
| General | |
| Control pulse outputs | Close, open 1 and open 2 (Galvanically insulated from earth and each other) |
| Time base inaccuracy | ±0.01 % of reading ±1 sample interval |
| Max. sample rate | 40 kHz |
| Measurement time | Up to 10 s |
| Non-bouncing switch | |
| Max. current | 60 A AC / DC, pulse ≤ 20 ms |
| Max. continuous current | 5 A |
| Duration | User configurable in steps of 1 ms |
| Delay | User configurable in steps of 1 ms |
| 1 With standard 5 m test leads and floating test object | |
| Current measurement | |
| Measurement range | ±80 A |
| Resolution | 16 bits |
| Inaccuracy | ±2 % of reading ±0.1 % of range |
| Voltage measurement | |
| Max. voltage | 250 V AC, ±300 V DC |
| Measurement range | ± 400V |
| Resolution | 16 bit |
| Inaccuracy | ±1 % of reading ±0.1 % of range |
| Timing M/R section | |
| General | |
| No. of channels | 3,6 or 12 selectable at ordering |
| Time base inaccuracy | ±0.01 % of reading ±1 sample interval |
| Min. detected contact bounce | 0.05 ms |
| Max. sample rate | 40 kHz |
| Measurement time | Up to 10 s |
| Timing of main and resistor contacts | |
| Open circuit voltage | Toggling ±12 V ±10 % |
| Short cicuit current | 22 mA ±10 % |
| 50/60 Hz interference suppression | |
| Active Interference Suppression, Megger patent | |
| Transient disturbance suppression | |
| Smart digital filter | |
| Status threshold | |
| User configurable thresholds | |
| Main | Closed < 10 Ω < Open (Factory default) |
| Main and resistor | Main < 10 Ω < PIR < 2 kΩ < Open (Factory default) |
| PIR resistance measurement | |
| Supported PIR types | Linear PIR |
| Measurement range | 10 Ω – 10 kΩ |
| Inaccuracy | ±5 % of reading ±0.1 % of range1 |
| PIR resistance measurement | |
| Supported PIR types | Linear PIR |
| Measurement range | 10 Ω – 10 kΩ |
| Inaccuracy | ±5 % of reading ±0.1 % of range1 |
| Voltage measurement (Only TIMING M/R, DRM/VDS inputs) | |
| Measurement ranges | ±50 V and ±2.5 V |
| Resolution | 16 bits |
| Inaccuracy | ±1 % of reading ±0.1 % of range |
- Mid-range circuit breaker analyser providing a new level of accuracy to your standard measurements
- Intuitive operation offers final measurement results with a minimum of user interaction
- Measurement performance inherited from market leader Megger TM series circuit breaker analysers
- Instrument and accessories designed for the most demanding field conditions
- Easy-to-use and intuitive interface
Comments are closed.