The NEW Megger TTRU3 transformer turns ratiometer uses a revolutionary design to perform a complete series of measurements on a transformer, including 3Ø step up turns ratio testing (patented).
3Ø voltage output offers numerous advantages to testing with today’s busy schedules. Features include:
- Validation and recognition of phase relationship of vector groups facilitated with on screen vector rotation and Auto vector recognition.
- Accurate measurement of phase shift relationship (for phase shifting transformers and Zig Zag vector configurations).
- Faster testing – all 3 phases tested simultaneously
- More reliable – removes the requirement for internal relay switching which is a common cause of failure
The TTRU3 is an important tool for determining the mechanical condition of transformers. All ratio tests are performed in one instrument, with only one 3Ø lead-set connection. The TTRU3 utilizes the latest 7 inch (180 mm) color touch display, as well as an optional printer so you never lose your results. This is complimented with remote control which can be operated from your PC, as well as the ability to download results to a USB memory device.
SPECIFICATIONS
Input Power
90-264VAC, 47-63Hz, 250VA MaxOutput
Voltage: 3Ø, 1 - 48VAC, up to 250V on PrimaryFrequency: 50-480Hz
Current: 0.1mA - 1A, Max 2A @ 48V
Turns Ratio Measurement Methods
3Ø Step Up3Ø Step Down
1Ø Step Up
1Ø Step Down
Turns Ratio Range and Accuracy - Guaranteed accuracy from -20°C to +50°C
Step Down Excitation- 25-48V
- ±0.05% 0.8 - 1000
- ±0.10% 1001 - 2000
- ±0.30% 2001 - 15000
- ±1% 15001 – 50000
- 1-24V
- ±0.10% 0.8 - 1000
- ±0.20% 1001 - 2000
- ±0.60% 2001 - 15000
- Step Up Measurement
-
- 25-250V
- ±0.05% 0.8 - 200 (most Power Tx)
-
- 1-24V
- ±0.10% 0.8 - 200
- 5 digit resolution
Excitation Current Measurement
Resolution: 0.1mA 0.1mA - 100mA1mA 101-2000mA
Accuracy: ± 1% ±0.1 mA
Frequency Measurement
Resolution: 0.1 HzAccuracy: ±0.1% ±0.1 Hz
Transformer Phase Measurement
Range: 0 - 360 DegreesAccuracy: ± 0.05 Degrees
Environmental
Operating -20°C to +50°C (-4°F to +122°F)Storage -30°C to +70°C (-22°F to +158°F)
Relative Humidity 0-90%, non-condensing
Ingress Protection
TTRU3: IP 51 TTRU3 in transit case: IP 67Regulatory
- Safety
- IEC 61010-1:2010 + AMD1:2016
- EMI/EMC
- RoHS2
- EN50581>
- Vibration/Drop/Shock
- MIL-STD-810G
TYPICAL PROBLEMS FOUND USING THE TTRU3
- Loose connections
- Turn-to-turn shorts
- Broken Strands
- Winding deformation
- Tap changer contact problems
- Core Problems
TESTING PERFORMED
- All with one instrument and 3Ø lead-set connection!
- Ratio - 3Ø Step Up testing for power transformers
- PhaBse shift & phase deviation
- Polarity
- Magnetic balance/flux distribution
- Excitation current characteristics
- Auto vector detection/recognition
FEATURES AND BENEFITS
- 3Ø test voltage - fast testing of all transformers
- Patented 3Ø Step Up Testing
- Confirm expected nameplate vector configuration
- Ability to measure actual vs expected phase shift
- Unique kelvin clamps with adjustable 3-inch jaw
- Banana plug input for connection to terminal blocks
- Turns ratio % error vs nameplate with pass/fail
- PC interface via USB for remote control operation and downloading of test results
STEP UP - TURNS RATIO TESTING SIMPLIFIED
From IEEE C57.152 2013, under requirement for ratio measurement, the standard states: The term “transformer turns ratio” (TTR) meter is commonly used to describe these instruments even though the actual turns ratio is not being measured.
Now you can measure “transformer turns ratio” as described in the standard with the new TTRU3. No need for higher voltage, heavy instruments that are more expensive and complex to operate - the TTRU3 automatically chooses the best test voltage and gives you the correct ratio the first time! All with one instrument and 3Ø lead-set connection!
STEP UP TURNS RATIO TESTING
The technology within the TTRU3 is based on patented 3Ø step up ratio testing. When compared to traditional 1Ø step down test instruments, the TTRU3 removes the inaccuracy associated with test voltage. The user is no longer required to know the “proper” test voltage required to obtain a “valid” result. This makes testing much easier, as repetition of testing at proper voltage is no longer required
The technology within the TTRU3 is based on patented 3Ø step up ratio testing. When compared to traditional 1Ø step down test instruments, the TTRU3 removes the inaccuracy associated with test voltage. The user is no longer required to know the “proper” test voltage required to obtain a “valid” result. This makes testing much easier, as repetition of testing at proper voltage is no longer required
Comments are closed.